Series 625 monitoring systemSeries 625 physical layout and dimensions
Anville Instruments - Process monitoring and data logging

Anville series 625 data acquisition system

The Anville Series 625 is a compact modular data acquisition unit, designed to provide accurate and reliable data measurement whilst operating in the harshest environments

Available in 8, 16 and 24 channel versions with analogue inputs, digital inputs analogue outputs (4 channels per slot) or digital outputs. All analogue input channels are individually configurable.

The unit features RS485 communications employing either MODBUS/RTU or ANSI-X3 protocols. TCP/IP MODBUS can be fitted as an option. An RS232 port is used for configuration.

Key features:

Input channels

Analogue inputs (8 channels per slot)

Thermocouples
(Characterised)
J: -200°C to 1100°C
K: -200°C to 1370°C
T: -200°C to 387°C
S: 0°C to 1768°C
R: 0°C to 1684°C
B: 150°C to 1820°C
E: -250°C to 1000°C
U: User configurable characterisation
RTD (2/3 wire) Pt100: -200°C to 400°C
Voltage (scaleable) ±20mV, ±50mV, ±100mV
±200mV, ±500mV
±1.00V, ±2.00V, ±5.00V
±10V, ±20V
Current (scaleable) 0-25.6mA (measured across 100Ω burden resistor
Isolation ±300VDC inter-channel/system
Multiplexing Opto-isolated dual pole N/O SSR
Input type Differential
Impedance >1MΩ (100k above 2V)
Input filter Low pass
Rejection at 50Hz: >60dB
Common mode rejection >140dB @ 50Hz
240VAC to earth
Temperature coefficient ±50ppm/°C
Scan rate 3s for 24 channels
Resolution Sigma-delta converter
Maximum 16 bits
Accuracy ±0.1% of span
CJ compensation 30:1 ambient rejection

Digital inputs (8 channels per slot)

Isolation ±300VDC inter-channel/system
Low range 10-50V (2-10mA) AC/DC
High range 50-240VAC
Modes Status / counter (software selectable pre-scaling
Count frequency 20Hz with de-bounce
200Hz without de-bounce

Output channels

Digital outputs (8 channels per slot)

Solid state Opto SSR, 240VAC/DC @ 320mA perk/100mA continuous N/O, N/C and 4 channels C/O
Modes On/off, software selectable PWM

Analogue outputs (4 channels per slot)

Voltage 0-10VDC up to 2mA
Current Constraining 0-20mA @ 15-28VDC
Isolation ±300VDC inter-channel/system
Resolution Unipolar 12 bit

Electrical

Supply voltage Regulated 24VDC @ 60mA
Isolation 500VDC

Mechanical

Dimensions 90mm x 140mm x 75mm
Weight 500g (average)
Casing Reinforced polycarbonate
Fixing DIN rail symmetrical 35mm (conforming to EN50022/BS5584)
Protection IP40

Communications

Ports (isolated) 1 x RS485/422 (2, 3, 4 wire)
Ports (unisolated) 1 x RS232 (RJ11) for configuration and local connection
Baud rates Jumper selectable from 1200 Baud to 768 kBaud
Protocols Jumper selectable between MODBUS/RTU and JBUS

Environmental

EMC Emissions comply with EN50081-1
Immunity complies with EN50082-2
Safety Compliant with EN60950
Ambient limits Storage -20°C to 70°C
Operating -10°C to 50°C
Humidity: 20% to 90% (non-condensing)